Basic function
|
|
Highest frequency
|
Vector control: 0~500Hz; V/F control: 0~500Hz
|
|
Carrier frequency
|
0.8kHz~12kHz. The carrier frequency can be automatically adjusted according to the temperature characteristics.
|
|
Input frequency resolution
|
Digital setting: 0.01Hz; Analog setting: max frequency × 0.025%
|
|
Control mode
|
Open-loop vector (SVC), V/F control
|
|
Start torque
|
G Type: 0.5Hz/150% (SVC); 0Hz/180% (FVC)
|
|
Speed range
|
1:100 (SVC)
|
|
Speed control accuracy
|
±0.5% (SVC)
|
|
Torque control accuracy
|
±5% (FVC)
|
|
Overload capacity
|
G Type: 150% Rated current 60sec; 180% Rated current 3sec
|
|
Torque boost
|
Automatic torque increase; Manual torque increase: 0.1%~30.0%
|
|
V/F curve
|
Three types: linear type; multi-point type; the nth power of V/F curve (1.2 power, 1.4 power, 1.6 power, 1.8 power)
|
|
V/F Separation
|
Linear or S curve of ACC/DEC ways. Four types of ACC/DEC Time, ACC/DEC time range is 0.0~6500.0s
|
|
ACC/DEC curve
|
Two types: full separation, half of separation
|
|
DC brake
|
DC brake frequency: 0.0Hz~max frequency; Brake action current: 0.0%~100.0%; Brake time: 0.0s~36.0s
|
|
JOG control
|
JOG frequency range: 0.0Hz~50.00Hz; JOG speed-up/down time: 0.0s~6500.0s
|
|
Simple PLC multi-stage speed running
|
Via built-in PLC or control terminal, can realize max 16 stage speed running
|
|
Built-in PID
|
Can realize process control close-loop system conveniently
|
|
Auto adjust voltage (AVR)
|
When grid voltage changes, can keep output voltage steadily automatically
|
|
During under-voltage and over-voltage speed control
|
During running, limit current and voltage automatically, protect from tripping off frequently for overvoltage and overcurrent
|
|
Quick current-limit function
|
Reduce overcurrent error to max extent, protect inverter normal running
|
|
Torque limitation and control
|
"Digger" feature, inverter could limit torque automatically, prevent overcurrent tripping off; close-loop vector can realize torque control
|
|
Personalization function
|
|
Outstanding perform
|
Using high-perform current vector control
|
|
Instantaneous stop not stop
|
During instant power-off, by motor feedbacking energy, inverter compensates voltage-drop to keep running for short time
|
|
Timing control
|
Timing control function; setting time range: 0.0min~6500.0min
|
|
Command source
|
Control panel, control terminal, communication; can be switched by several modes
|
|
Frequency source
|
10 types of frequency sources: digital setting, analog voltage setting, analog current setting, pulse setting, communication setting, can be switched by several methods
|
|
Auxiliary frequency sources
|
10 types of auxiliary frequency source, can realize auxiliary frequency trimming, frequency combining flexibly
|
|
Running display and keypad
|
|
Input terminal
|
Standard: 4 digital input terminal; 1 supports 0~10V voltage input or 0~20mA current input
|
|
Output terminal
|
1 relay output terminal
|
|
LED display
|
LED display: display parameter
|
|
Press-key locking and function selection
|
Realize press-key partial or full lacking, define part press-key function range, to avoid wrong operation
|
|
Protection function
|
Power-on motor short circuit test, output phase-loss protection, over-current protection, over-voltage protection, under-voltage protection, overheat protection, overload protection etc
|
|
Optional parts
|
Differential PG card, open collector PG card, rotary transformer PG card
|
|
Environment
|
|
Application site
|
Indoor, without direct sunlight, no powder, corrosive gas, combustion air, oil dust, water steam, water drop or salt etc
|
|
Altitude level
|
Less than 1000m
|
|
Environment temperature
|
-10℃~+40℃ (During 40℃~50℃, please reduce capacity to use)
|
|
Humidity
|
<95% RH, no water drop condensed
|
|
Optional parts
|
|
LED display
|
The keyboard can be imported from outside, and is compatible with the keyboard interface of the company's 510A and 510H frequency converters
|