| Model | Power capacity (kVA) | Input current (A) | Output current (A) | Match motor (kW) |
|---|---|---|---|---|
| Single phase: 220V, 50/60Hz | ||||
| EV510H-0004G-S2 | 1.0 | 5.4 | 2.3 | 0.4 |
| EV510H-0007G-S2 | 1.5 | 8.2 | 4.0 | 0.75 |
| EV510H-0015G-S2 | 3.0 | 14.0 | 7.0 | 1.5 |
| EV510H-0022G-S2 | 4.0 | 23.0 | 9.6 | 2.2 |
| Three phase: 380V, 50/60Hz | ||||
| EV510H-0007G-T4 | 1.5 | 3.4 | 2.1 | 0.75 |
| EV510H-0015G-T4 | 3.0 | 5.0 | 3.8 | 1.5 |
| EV510H-0022G-T4 | 4.0 | 5.8 | 5.1 | 2.2 |
| EV510H-0037G/0055P-T4 | 5.9 | 10.5 | 9.0 | 3.7 |
| EV510H-0055G/0075P-T4 | 8.9 | 14.6 | 13.0 | 5.5 |
| Item | Specification |
|---|---|
| Highest frequency | Vector control: 0~500Hz; V/F control: 0~500Hz |
| Carrier frequency | 0.8kHz~12kHz The carrier frequency can be automatically adjusted according to the temperature characteristics. |
| Input frequency resolution | Digital setting: 0.01Hz; Analog setting: maximum frequency × 0.025% |
| Control mode | Open-loop vector (SVC); V/F control |
| Start torque | G Type: 0.5Hz/150% (SVC); P Type: 0.5Hz/100% |
| Speed range | 1:100 (SVC) |
| Speed control accuracy | ±0.5% (SVC) |
| Overload capacity |
G Type: 150% Rated current 60sec; 180% Rated current 3sec P Type: 120% Rated current 60sec; 150% Rated current 3sec |
| Torque boost | Automatic torque increase; Manual torque increase 0.1%~30.0% |
| V/F curve | Three types: linear type; multi-point type; the nth power of V/F curve (1.2 power, 1.4 power, 1.6 power, 1.8 power, 2 power) |
| ACC/DEC curve | Two types: full separation, half of separation |
| DC brake |
DC brake frequency: 0.00Hz~max frequency Brake time: 0.0s~36.0s Brake action current: 0.0%~100.0% |
| JOG control | JOG frequency range: 0.00Hz~50.00Hz. JOG speed-up/down time: 0.0s~6500.0s |
| Simple PLC multi-stage speed running |
Via bul-in PLC or control terminal can realze max 16 stage speed running
|
| Built-in PID | Can realize process control closed-loop system conveniently |
| Auto adjust voltage (AVR) | When grid voltage changes, can keep output voltage steadily automatically |
| Overcurrent and overvoltage speed control | During limit current and voltage automatically, protect from tripping off frequently for overvoltage and overcurrent |
| Quick current-limit function | Reduce overcurrent error on max extent, protect inverter normal running |
| Torque limitation and control | "Digger" feature, inverter could limit torque automatically, prevent overcurrent tripping off; close-loop vector can realize torque control |
| Outstanding performance | Using high-performance vector control |
| Instantaneous stop not stop | During instant power-off, by motor feedback energy, inverter compensates voltage-drop to keep running for a short time |
| Timing control | Timing control function: setting time range: 0.0min~6500.0min |
| Command source | Control panel, control terminal, communication; can be switched by several modes |
| Frequency source / Auxiliary frequency sources | Digital setting, analog voltage setting, analog current setting, pulse setting, communication setting, can be switched by several methods |
| Input terminal |
5 digital input terminals, one of them supports max 100KHz HS pulse input (apolegamy). 2 analog input terminals; AI2 supports 0~10V voltage input; AI1 supports 0~10V voltage input or 0~20mA current input |
| Output terminal |
1 high-speed pulse output terminal (optional open collector), supports 0~100KHz pulse (apolegamy). 1 relay output terminal. 1 analog output terminal, supports 0~20mA current output |
| LED display | Can display parameters |
| Press-key locking and function selection | Realize press-key partial or full locking, define part press-key function range, to avoid wrong operation |
| Protection function | Power-on motor short circuit test, output phase-loss protection, over-current protection, over-voltage protection, under-voltage protection, overheating protection, overload protection, overload protection etc |
| Application site | Indoor, without direct sunlight, no powder, corrosive gas, combustion air, oil dust, water steam, water drop or salt etc |
| Altitude level | Less than 1000m, Derating above 1000m, Rated output current decreases by 1% every 100m |
| Environment temperature | -10℃~+40℃ (During 40℃~50℃, please reduce capacity to use) |
| Humidity | ≤95%RH, no water drop condensed |
|
Model
|
Outlinesize (mm)
|
Installation hole
|
|||
|
B
|
W
|
H
|
D
|
||
|
EV510H-0004G-S2
|
155
|
84
|
170
|
127
|
Ф5.7
|
|
EV510H-0007G-S2
|
|||||
|
EV510H-0015G-S2
|
|||||
|
EV510H-0022G-S2
|
|||||
|
EV510H-0007G-T4
|
|||||
|
EV510H-0015G-T4
|
|||||
|
EV510H-0022G-T4
|
|||||
|
EV510H-0037G/0055P-T4
|
183
|
91
|
193
|
142
|
Ф4.7
|
|
EV510H-0055G/0075P-T4
|
|||||